EasyManuals Logo
Home>Johnson Controls>Air Conditioner>100 Series

Johnson Controls 100 Series User Manual

Johnson Controls 100 Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #105 background imageLoading...
Page #105 background image
JOHNSON CONTROLS
105
SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
• The BAS sends a 0–100% command to the IPU
board (BACnet point AV52).
• Once the BAS command is greater than the ex-
haust output for fan start, the exhaust fan VFD is
started.
• Once the BAS command is less than the xhaust
output for fan stop, the exhaust fan VFD is
stopped.
Return Fan Assembly
• The Series 100 unit can be ordered with an op-
tional return fan assembly.
• The return fan assembly can be ordered as either
return fan without exhaust or return fan with ex-
haust.
• A return fan assembly is typically used on systems
where the return duct static pressure is greater
than 0.75 iwg.
• A return fan assembly assists the supply fan in
drawing the proper amount of return air from the
building.
• The return fan runs whenever the supply fan is
ON.
• On the Series 100 units, the return fan assembly
has one VFD controlling two separate return fan
assemblies.
• When operating properly, the return fan assem-
blies are spinning in opposite directions.
Return Fan without Exhaust Sequence of
Operation
• Power exhaust type must be set to Return Fan
without Exhaust in the OPTIONS-EXHAUST
menu.
• The return fan speed is controlled by the active
return fan plenum pressure setpoint.
• In this sequence, the return plenum pressure
setpoint is a xed value of 0.05 iwg.
• When the supply fan starts, the return fan starts
as well.
• The IPU board monitors the return fan plenum pres-
sure and controls the speed of the return fan VFD
up/down to maintain the return fan plenum pressure
setpoint.
Return Fan with Exhaust Sequence of
Operation
• Power exhaust type must be set to Return Fan
with Exhaust in the OPTIONS-EXHAUST menu.
• Building pressure setpoint must be set in the SET-
POINTS-EXHAUST menu.
• Return pressure high setpoint must be set in the
SETPOINTS-SUPPLY SYSTEM menu.
• The return fan speed is controlled by the active
return fan plenum pressure setpoint.
• When the supply fan starts, the return fan starts
as well.
• The return fan speed is controlled as follows:
1. Building pressure less than the building pres-
sure setpoint
• The return fan speed is controlled to the
fixed return plenum pressure setpoint of
0.05 iwg.
2. Building pressure greater than the building
pressure setpoint:
• The return fan speed is controlled to the
active return plenum pressure setpoint.
• As the building pressure rises above the
building pressure setpoint, the Active
return plenum pressure setpoint starts to
reset to a higher value.
• When the exhaust demand reaches 100%,
the active return plenum pressure setpoint
is equal to the return pressure high
setpoint. See Figure 55 on page 105.
LD28131
FIGURE 55 - ACTIVE RETURN PLENUM PRESSURE
SETPOINT VERSUS EXHAUST OUTPUT

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals