EasyManuals Logo

Johnson Controls 100 Series User Manual

Johnson Controls 100 Series
182 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #63 background imageLoading...
Page #63 background image
JOHNSON CONTROLS
63
SECTION 5 – SEQUENCE OF OPERATION
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
5
• When the unit has a heating source installed:
• Occ zone heating setpoint must be set in the
SETPOINTS-HEATING menu (zone control
method is wired or Comm Zone Temperature).
• 1st and 2nd stage heating setpoints must be
set in the SETPOINTS-HEATING menu.
• The IPU board must have a valid zone temperature
reading if zone control method is set to Wired or
Comm Zone Temperature.
Supply Fan
• The supply fan must be running before any other
unit operation is allowed.
• The IPU board monitors the status of an APS to de-
termine the supply fan status.
• The APS must be closed, which proves supply fan
status before cooling, heating, or any other operation
is permitted.
• The supply fan is started whenever there is a de-
mand for cooling or heating, regardless of occu-
pancy.
• The supply fan can be operated continuously in
the Occ mode if continuous ventilation is User En-
abled in the PROGRAM-VENTILATION menu.
• The supply fan is started if zone control method is
set to Staged and there is a demand for G terminal
either from a thermostat or from the BAS.
Supply Fan Status
• The unit uses an APS to determine supply fan sta-
tus.
• The APS is a diaphragm type switch that closes at
approximately 0.30 iwg.
• The APS is mounted above the supply fan blower
assembly.
• The APS senses the static pressure through a fac-
tory installed tube that passes through the supply
fan wall into the next section of the unit.
• The APS needs to close and prove supply fan sta-
tus within 45 seconds after the supply fan is com-
manded on.
• Failure to prove supply fan status within 45 sec-
onds causes a Supply Fan Lockout to occur.
• A Supply Fan Lockout also occurs when the APS
opens for more than 2 seconds after fan status is
proven to be running.
As per ASHRAE 90.1-2010, Series 100 units has a
supply fan VFD installed to control the speed of the
supply fan based on cooling/heating demands or stand-
by operation when configured for SZVAV.
SZVAV Minimum Speed
• User adjustable setpoint that can be found under
SETPOINTS-SUPPLY SYSTEM menu.
• This is the speed the supply fan operates at per
Table 21 on page 63.
TABLE 21 - SZVAV SUPPLY FAN SPEED
STATUS UNIT MODE
Supply fan at SZVAV minimum speed
Occ Standby (continuous ventilation is User Enabled)
Occ/Unocc Cooling Low
Supply fan speed is modulating up/down
Unit mode switches from Occ/Unocc Cooling Low to Occ/Unocc Cooling High
At this point the supply fan speed starts to increase/decrease as the cooling
demand increases/decreases
Supply fan speed at 100%
Occ Cooling High (see above)
Unocc Cooling High (see Above)
Occ Heating Low
Occ Heating High
Unocc Heating Low
Unocc Heating High
Comfort Vent Cool
Comfort Vent Heat
Morning Warm-Up
Supply fan is OFF
Occ Standby (continuous ventilation is User Disabled)
Unocc Standby

Table of Contents

Other manuals for Johnson Controls 100 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls 100 Series and is the answer not in the manual?

Johnson Controls 100 Series Specifications

General IconGeneral
BrandJohnson Controls
Model100 Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals