JOHNSON CONTROLS
133
SECTION 6 – USER INTERFACE CONTROL CENTER
FORM 100.50-NOM12
ISSUE DATE: 04/02/2019
6
TABLE 51 – SERVICE (CONT'D)
DISPLAY TEXT TYPE ID VALUE RANGE LOCATION DESCRIPTION
STG GAS
FURN 1 LOW
Digital
Output
TB3-2 On / Off I/O Board
Status Of Staged Gas Heat Digital
Output To Stage 1 Low
STG GAS
FURN 1 HIGH
Digital
Output
TB3-3 On / Off I/O Board
Status Of Staged Gas Heat Digital
Output To Stage 1 High
STG GAS
FURN 2 LOW
Digital
Output
TB3-4 On / Off I/O Board
Status Of Staged Gas Heat Digital
Output To Stage 2 Low
STG GAS
FURN 2 HIGH
Digital
Output
TB3-5 On / Off I/O Board
Status Of Staged Gas Heat Digital
Output To Stage 2 High
STG GAS
FURN 3 LOW
Digital
Output
TB3-7 On / Off I/O Board
Status Of Staged Gas Heat Digital
Output To Stage 3 Low
STG GAS
FURN 3 HIGH
Digital
Output
TB3-8 On / Off I/O Board
Status Of Staged Gas Heat Digital
Output To Stage 3 High
MOD GAS
FURN 1A LOW
Digital
Output
TB3-2 On / Off I/O Board
Status Of Mod Gas Heat Digital Output
To Stage 1A Low
MOD GAS
FURN 1A HI
Digital
Output
TB3-3 On / Off I/O Board
Status Of Mod Gas Heat Digital Output
To Stage 1A High
MOD GAS
FURN 2 LOW
Digital
Output
TB3-4 On / Off I/O Board
Status Of Mod Gas Heat Digital Output
To Stage 2 Low
MOD GAS
FURN 2 HIGH
Digital
Output
TB3-5 On / Off I/O Board
Status Of Mod Gas Heat Digital Output
To Stage 2 High
MOD GAS
FURN 3 LOW
Digital
Output
TB3-7 On / Off I/O Board
Status Of Mod Gas Heat Digital Output
To Stage 3 Low
MOD GAS
FURN 3 HIGH
Digital
Output
TB3-8 On / Off I/O Board
Status Of Mod Gas Heat Digital Output
To Stage 3 High
MOD GAS
FURN 1B
Digital
Output
TB3-9 On / Off I/O Board
Status Of Mod Gas Heat Digital Output
To Stage 1B
PUMP DOWN LLSV 1
Digital
Output
TB5-2 On / Off I/O Board
Status Of Pump Down Solenoid Llsv 1
Digital Output
PUMP DOWN LLSV 2
Digital
Output
TB5-4 On / Off I/O Board
Status Of Pump Down Solenoid Llsv 2
Digital Output
PUMP DOWN LLSV 3
Digital
Output
TB5-6 On / Off I/O Board
Status Of Pump Down Solenoid Llsv 3
Digital Output
SUPPLY FAN
OUTPUT
Digital
Output
TB1-2 On / Off Always Status Of Supply Fan Digital Output
RETURN FAN OUTPUT
Digital
Output
TB1-4 On / Off I/O Board Status Of Return Fan Digital Output
EXHAUST FAN OUTPUT
Digital
Output
TB1-4 On / Off I/O Board
Status Of Exhaust Fan Or Return Fan
Digital Output
VAV HEAT RELAY
Digital
Output
TB1-12 On / Off I/O Board
Status Of The Digital Output For The
Vav Heat Relay
FAN FAULT
Digital
Output
TB1-6 Okay / Faulted I/O Board
Digital Output That Is Generated When
There Is A Supply Fan Fault
COOL/HEATING FAULT
Digital
Output
TB1-8 On / Off I/O Board
Digital Output That Is Generated When
There Is A Cooling/Heating Fault
SENSOR/MISC FAULT
Digital
Output
TB1-10 On / Off I/O Board
Digital Output That Is Generated When
There Is A Sensor/Misc Fault
SUPPLY FAN VFD
SPEED
Analog
Output
TB9-1
0-10
Volt Dc
I/O Board Analog Output To The Supply Fan VFD