7.11 Summer/wintertime adjustment(AFR)
MULTICAL®603isavailablewithconfigurationforDST(DaylightSavingTime~summer/wintertime).Themeter’s
countrycodedeterminestheDSTconfigurationalgorithm,so thatitcorrespondstotheDS Tregulationsofthecountry,
forwhichthemeterisintended.IfthemeterisconfiguredwithDSTandyoudonot
wanttouseit,theDSTfunction
canbedisabledinthePCprogramMETERTOOLHCW.TheDSTfunctionhasdirectinfluenceonthemeter’sinternal
clock andtimecontrolledtarifflimits. Time stampsfor loggingsof events andvalues are savedin standardtime
togetherwithinformationonthe
currentDSToffset.ThecurrentDSToffsetisappliedtoallloggedtimestampswhen
theDSTfunctionisactive,theappliedDSToffsetisremovedfromtimestampsiftheDSTfunctionisdeactivatedinthe
meterandviceversaiftheDSTfunctionisreactivated.
DSTandtariffs:The
timecontrolledtariffisinfluencedbytheDSToffset.Theenteredtarifflimits,forexample,willbe
movedanhourforwardatDSTstartandanhourbackwardsattheendofDST(Danishexample).IftheDSTfunctionis
disabledafteraperiodinoperation,thetimelimitswill
alwaysfollowstandardtime.Accumulatedenergyinthetariff
registersremainsunchangedandthusreflectsthetimelimitswithenabledDSTfunction.Thesameappliesviceversa
iftheDSTfunctionisreactivated.
DSTandloggers:Theloggingtimefollowsnormaltime.Forexample,ameterwithenabledDSTfunction,which
logs
dataat00.00duringwintertime,willlogdataat01.00a.m.duringsummertime(Danishexample).IftheDST
functionisdisabledafterdeliveryandhistoricalloggervaluesaresubsequentlyread,theDSToffsetofprevious
valueswillreflectthenewconfigurationandberemovedfromthetime
stamp.Seeexampleinbelowtable.Read
loggingtimeswillalwaysreflectthecurrentDSTstatus.
DSTenabled DSTdisabled
Logstargetdate Loggingtime Loggingtime
1January 00:00 00:00
1February 00:00 00:00
1March 00:00 00:00
1April 01:00 00:00
1May 01:00 00:00
1June 01:00 00:00
1July 01:00 00:00
1August 01:00 00:00
1September 01:00 00:00
1October 01:00 00:00
1November 00:00 00:00
1December 00:00 00:00

DSTandmax/min.values:Timestampsonloggingofmax/min.valuesfollowstandardtime.Ifthetimestampofavalue
isread,itwillbestatedwithcurrentDSToffset.IftheDSTfunctionisdisabledafterdelivery,theDSToffsetwillbe
removedfromthetimestampsof
historicalvaluesasitisdonewiththeloggers.
DSTandread outofloggingdata:Datacaneitherbereadfromaregister,whichincludestimeinstandardtimeandDST
offsetastwoseparateparameters,oralternativelyfromaregister,whichincludestimecomprisingDSToffsetasa
parameter.If
theDSTfunctionisdisabledafterdelivery,informationontheDSToffsetwillberemovedfromtime
stampsrelatedtothehistoricalvalues.

Table of Contents

Other manuals for Kamstrup MULTICAL 603

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup MULTICAL 603 and is the answer not in the manual?

Kamstrup MULTICAL 603 Specifications

General IconGeneral
Flow SensorUltrasonic
Battery LifeUp to 16 years
Power SupplyBattery
Communication OptionsM-Bus, Wireless M-Bus, Modbus, BACnet
DisplayLCD
ApplicationHeating and Cooling
Pressure RatingPN16
ApprovalMID
AccuracyClass 2
Ambient Temperature Range55°C
Housing MaterialBrass