MULTICAL®603
54
KamstrupA/S∙Technicaldescription∙55122029_A1_GB_06.2017
3.3 Data
Thecountrycodeisselectedasthelasttwocharactersofthemeter’sstaticpartofthetypenumber.
Staticdata
603xxxx
‐
Dynamicdata
xxxxxxxx
Writtenonthe
meter’sfront
Canbedisplayed

Type603‐ □ XX‐
Inadditiontodefiningthelanguageonthemeterlabelaswellasapprovalandverificationmarks,thecountrycodeis
alsousedtocontroltheconfigurationofanumberofmeterdata.
DuringproductionofMULTICAL®603itisprogrammedwithanumberofmeasuringvalues
inthefieldslistedoverleaf.
Unlesstheorderincludesspecificrequirementsastoconfiguration,MULTICAL®603besuppliedwiththedefault
valuesfromthetable.
Automatic Tobestatedinorder Standard
Serialno.(S/N)
1
(Seeparagraph3.4)
80,000,000‐
Customerno.
DisplayNo.1=8digitsMSD
DisplayNo.2=8digitsLSD
‐
Upto16digits
Customerno.equalto
S/N
Yearlytargetdate1(MM.DD)
‐ MM=112andDD=131
Dependsoncountry
code
Monthlytargetdate1(DD)
‐ DD=131
Yearlytargetdate2(MM.DD)
‐
MM=112andDD=131+
00.00(disabled)
2
Monthlytargetdate2(DD)
‐
DD=131+
00(disabled)
2
Averagingperiodformin./maxof
power(P)andflow(Q)
(Seeparagraph7.5)
‐ 1…1440min. 60min.
AveragingperiodofCP
(Seeparagraph7.2)
‐ 5…30days 7days
hc
Heat/coolingshift
Onlyactiveifmetertype6is
selected
(Seeparagraph7.4)
‐
2…180.00C+250.00C
3
Heat/cooling,metertype
6:
25.00C
Date/time
20YY.MM.DD/
hh.mm.ss
GMT12.0hours
(Canbedefinedathalfhour
intervals)
‐
GMToffset‐
Dependsoncountry
code
PrimaryaddressofMBus,
ModbusandBACnet
4
‐ Address0250
Last23digitsof
customernumber
MBusIDno.
(usedforsecondaryaddress)
‐ ‐ Customerno.
wMBusIDno.‐ Serialnumber