7 Calculatorfunctions
7.1 Applicationtypesandenergyc alculations
MULTICAL
603operateswith15differentenergyformulas,E1,E2,E3,E4,E5,E6,E7,E8,E9,E10,E11,A1,A2,dEand
cE,whichareallcalculatedparallelwitheachintegration,irrespectiveofhowthemeterisconfigured.E8andE9are
usedasabasisofthecalculationof
averagetemperaturesofinletandoutlet,whereasE1andE3areusedforheat
andcoolingmeasurement,respectively.E4toE7areusedinanumberofenergyapplicationsthatareshownbelow.
A1andA2areusedasabasisfordiscount/surchargebasedontheoutlettemperature(seeparagraph7.1.3).
Formula
Exampleofapp lication Included inapp lication
no.
Registertype
E1=V1(t1‐t2)k
t1:Inlet/t2:Outlet
t1>t2 Heatenergy(V1ininletoroutlet) 1+2+3+4+5+6+8+10 LegalDisplay/Data/Log
E2=V2(t1‐t2)k
t2:Outlet
t1>t2 Heatenergy(V2inreturn) 2+7 Display/Data/Log
E3=V1(t2‐t1)k
t2:Inlet/t1:Outlet
t2>t1 Coolingenergy(V1ininletoroutlet) 1+11 LegalDisplay/Data/Log
E4=V1(t1‐t3)k
t1:Inlet
t1>t3 Forwardenergy: 7+9+11 Display/Data/Log
E5=V2(t2‐t3)k
t2:Inlet
t2>t3 Outletenergyortapfromoutlet 5+7+9 Display/Data/Log
E6=V2(t3‐t4)k
t3:Inlet
t3>t4 Tapwaterenergy,separate 3+6 Display/Data/Log
E7=V2(t1‐t3)k
t3:Outlet
t1>t3 Returnenergyortap fromflow 4+8 Display/Data/Log
E8=V1(m
3
)xt1‐Averagetemperatureininlet Seeparagraph7.1.2. Display/Data/Log
E9=V1(m
3
)xt2‐Averagetemperatureinoutlet Display/Data/Log
E10=V1(m
3
)xt3‐Averaget3inV1 Display/Data/Log
E11=V2(m
3
)xt3‐Averaget3inV2 Display/Data/Log
A1 t5>t2 Heatenergyatadiscount Seeparagraph7.1.3. Display/Data/Log
A2 t2>t5 Heatenergywithanaddition Display/Data/Log
dE=E4‐E5‐Differentialenergy 7 ‐
cE=E5‐E4‐Controlofdifferentialenergy 7 ‐
Symbolsusedinapplication fig u res
Temperature
sensor
Stopvalve Flowsensor
Calculator
Consumer,
e.g.radiators
Non‐returnvalve
Heatexchanger