10.11 Replacementofsupplymodule
YoucanswitchbetweenalltypesofsupplymodulesinMULTICAL®603.Forexample,itcanbeanadvantage,fora
periodoftime,toexchang eamainsconnectedsupplymoduleforbatteryinabuildingwhichhasvaryingmains
supplyduetorestorationorconstructionwork.Forsomemeterconfigurations
batterysupplyisnotapractical
option,e.g.inconnectionwithfrequentdatacommunication.However,itisalwayspossibletoswitchthemodule
typefrombatterysupplytomainssupplywithoutreconfiguringthemeter.
10.12 Databackupincaseofinterrup t ionofsupply
MULTICAL®603isfittedwithasmalllithiumbattery(BR1632)asbackupforthemeter’sinternalclockincaseof
interruptionofthesupply.Independentofthemountedsupply modulethemeterisequippedwithfunctionality
whichsavesallcurrentregistercountsincasethevoltageoftheinternal3.6VDC
supplyisbelow3.1VDC.Whenthe
supplyisreestablished,themetercontinuescountingfromthevalue,whichwassavedwhenthesupplywas
interrupted.
10.13 Danishregulatio ns formainsconnectionofmeters
Installationofmainsconnectedequipmentforregistrationofconsumption.
(www.sik.dk,SIKmessageElectricalInstallations27/09,February2009)
Theconsumptionofenergyandresources(electricity,heat,gasandwater)oftheindividualconsumeristoan
increasingextentregisteredbyelectronicmeters,andoftenequipmentforremotereadingandremotecontrolof
bothelectronicandnonelectronicmetersisused.
Generalregulationsforcarryingoutinstallationsmustbeobserved.
However,thefollowingmodificationsare
permitted:
Ifmeterorequipmentforremotereadingorremotecontrolisdoubleinsulated,itisnotnecessarytoextend
theprotectiveconductortotheconnectionpoint.Thisalsoappliesiftheconnectionpointisaplugsocket,
providedthatitisplacedin
acanningwhichissealableorcanbeopenedwithkeyortoolonly.
Ifmeterorequipmentusedforremotereadingandremotecontrolisconnectedtoasafetytransformermountedin
thepanelanddirectconnectedtothebranchconductor,noonoffswitchorseparateovercurrentprotectionin
eitherprimaryorsecondarycircuitisrequired,providedthatthefollowingconditionsarefulfilled:
Thesafetytransformermusteitherbeinherentlyshortcircuitprooforfailsafe.
Theconductoroftheprimarycircuitmusteitherbeshortcircuitprotectedbytheovercurrentprotectionof
thebranchconductoror
shortcircuitsafelyrun.
Theconductorofthesecondarycircuitmusthaveacrosssectionofatleast0.5mm²andacurrentvalue
whichexceedstheabsolutemaximumcurrentdeliverablebythetransformer.
Itmustbepossibletoseparatethesecondarycircuitbyseparators,oritmustappear
fromtheinstallation
instructionsthatthesecondarycircuitcanbedisconnectedatthetransformer’sterminals.
Generalinformation
Workonthefixed installation,includinganyinterventioninthegrouppanel,mustbecarriedoutbyanauthorized
electrician.
Itisnotrequiredthatserviceworkonequipmentcomprisedbythismessage
aswellasconnectionanddisconnection
oftheequipmentoutsidethepaneliscarriedoutbyanauthorizedelectrician.Thesetaskscanbecarriedoutby
personsorcompanies,whoprofessionallyproduce,repairormaintainequipmentifonlythepersoncarryingoutthe
workhasthenecessaryexpertknowledge.


Table of Contents

Other manuals for Kamstrup MULTICAL 603

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Kamstrup MULTICAL 603 and is the answer not in the manual?

Kamstrup MULTICAL 603 Specifications

General IconGeneral
Flow SensorUltrasonic
Battery LifeUp to 16 years
Power SupplyBattery
Communication OptionsM-Bus, Wireless M-Bus, Modbus, BACnet
DisplayLCD
ApplicationHeating and Cooling
Pressure RatingPN16
ApprovalMID
AccuracyClass 2
Ambient Temperature Range55°C
Housing MaterialBrass