EasyManuals Logo

Keysight Technologies N6900 Series User Manual

Keysight Technologies N6900 Series
358 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
STATus Subsystem
STATus
:OPERation
[:EVENt]? Queries the operation event register.
:CONDition? Queries the operation condition register.
:ENABle <value> Sets the operation enable register.
:NTRansiton <value> Sets the Negative transition filter
:PTRansiton <value> Sets the Positive transition filter
:USER<1|2>
:SOURce EXPRession<1-8>|NONE Selects an expression to drive the user-defined status bits.
:PRESet Presets all Enable, PTR, and NTR registers.
:QUEStionable<1|2>
[:EVENt]? Queries the questionable event register.
:CONDition? Queries the questionable condition register.
:ENABle <value> Sets the questionable enable register.
:NTRansiton <value> Sets the Negative transition filter
:PTRansiton <value> Sets the Positive transition filter
SYSTem Subsystem
SYSTem
:BBR
:EVENt <"string"> Adds an event string into the BBR event log.
:SNAPshot <value> Captures a data snapshot of the specified length.
:STATus? Returns the completion status of the snapshot in percent.
:STATe? Returns true (1) if the Black Box Recorder is logging.
:TIME? Returns the length of the Black Box Recorder data.
:COMMunicate
:LAN|TCPip:CONTrol? Returns the initial socket control connection port number.
:RLSTate LOCal|REMote|RWLock Configures the remote/local state of the instrument.
:DATE <yyyy>,<mm>,<dd> Sets the date of the system clock.
:ERRor? Reads and clears one error from the error queue.
:LFRequency? Returns the power-line reference frequency.
:LFRequency
:MODE AUTO|MAN50|MAN60 Specifies automatic or manual line frequency detection.
:PASSword
:FPANel
:RESet Resets the front panel lockout password to zero.
:REBoot Reboots the instrument to its power-on state.
:SECurity
:IMMediate Clears all user memory and reboots the instrument.
:SIGNal
Keysight N6900/N7900 Series Operating and Service Guide 35
1 Quick Reference

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Keysight Technologies N6900 Series and is the answer not in the manual?

Keysight Technologies N6900 Series Specifications

General IconGeneral
BrandKeysight Technologies
ModelN6900 Series
CategoryPower Supply
LanguageEnglish

Related product manuals