Approvals, standards and guidelines
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 143
10.4 UL approval
10.4.1 UL Specification (English version)
Maximum Ambient Temperature:
Electronic Adapter Ambient
INV M
α
2 0.25 ADP M
α
WDM
*
50 °C [122 °F]
INV M
α
2 0.37 ADP M
α
WDM
*
45 °C [113 °F]
INV Mα 2 0.55
ADP Mα WDM *
40 °C [104 °F]
INV M
α
2 0.75 ADP M
α
WDM
*
35 °C [95 °F]
* WDM = Wall mounting
Required Markings
Enclosure intended for use with field-installed conduit hubs, fittings or closure plates UL approved
in accordance to UL514B and CSA certified in accordance to C22.2 No. 18, environmental Type 1
or higher.
Suitable for use on a circuit capable of delivering not more than 5 kA rms symmetrical amperes,
240 V maximum and when protected by RK5 class fuses rated 15 A.
CAUTION: Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the Manufacturer Instructions,
National Electrical Code and any additional local codes.
All wiring terminals marked to indicate proper connections for the power supply, load and control
circuitry.
For instructions for operator and servicing instructions on how to mount and connect the products
using the intended motor connection adapter, please see chapter 3.3 and 9.1 in the operating
manual.
CAUTION: Use 75° C [167° F] wires only.
CAUTION: Use copper conductors only.
CAUTION: Motor overtemperature sensing is not provided by the drive.
Internal overload protection activates within 60 seconds of reaching 150 % of the motor full load
current.
For used in Canada: TRANSIENT SURGE SUPPRESSION SHALL BE INSTALLED ON THE LINE
SIDE OF THIS EQUIPMENT AND SHALL BE RATED TO 240 V (PHASE TO GROUND), SUITABLE
FOR OVERVOLTAGE CATEGORY III, AND SHALL PROVIDE PROTECTION FOR A RATED
IMPULSE WITHSTAND VOLTAGE PEAK OF 2.5 kV