Installation
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 33
DAMAGE TO PROPERTY POSSIBLE
Risk of damage to the drive controller.
Correct phase assignment must be observed when connecting the drive controller,
otherwise the motor may be overloaded.
The supplied assembly material can be used to connect core end sleeves and cable shoes.
Fig. 5 and 6 show the different connection options.
DANGER!
Risk of death due to electrical shock!
Death or serious injury!
De-energise drive controller and secure it against being restarted.
Unused open cable ends in the motor terminal box must be insulated.
If a thermal resistor (PTC or Klixon) is not used, the T1 and T2 bridging contacts supplied must
be connected (as described in chapter 3.3.1).
The cross-section of the supply line must be designed according to the transfer category and
maximum permitted current. The contractor commissioning the device must ensure protection for
the power line.
3.3.4 Short circuit and ground protection
The drive controller contains an internal short circuit and ground protection.