Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 103
5.5.3 Switching frequency
The internal switching frequency can be changed in order to control the power element. A high
setting reduces noise in the motor but results in increased EMC emissions and losses in the drive
controller.
34.030 Switching frequency Unit: Hz
Relationship
to parameter:
33.010
Parameter
manual:
P. xy
Transfer status:
2
min.:
1 Own value
(to be entered!)
max.: 4
def.: 2
Selection of the switching frequency for the drive controller:
1 = 16 kHz
2 = 8 kHz
4 = 4 kHz
5.5.4 Controller data
34.010 Control method Unit: integer
Relationship
to parameter:
33.001
34.011
Parameter
manual:
P. xy
Transfer status:
2
min.: 100 Own value
(to be entered!)
max.: 201
def.: 100
Selection of the control method:
100 = open-loop asynchronous motor
200 = open-loop synchronous motor
34.020 Flying restart Unit:
Relationship
to parameter:
34.021
Parameter
manual:
P. xy
Transfer status:
2
min.:
0 Own value
(to be entered!)
max.: 1
def.: 1
This parameter can be used to activate the flying restart.
0 = disable
1 = enable