EasyManua.ls Logo

Kostal INVEOR Drive Controller - Switching Frequency; Controller Data

Kostal INVEOR Drive Controller
156 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 103
5.5.3 Switching frequency
The internal switching frequency can be changed in order to control the power element. A high
setting reduces noise in the motor but results in increased EMC emissions and losses in the drive
controller.
34.030 Switching frequency Unit: Hz
Relationship
to parameter:
33.010
Parameter
manual:
P. xy
Transfer status:
2
min.:
1 Own value
(to be entered!)
max.: 4
def.: 2
Selection of the switching frequency for the drive controller:
1 = 16 kHz
2 = 8 kHz
4 = 4 kHz
5.5.4 Controller data
34.010 Control method Unit: integer
Relationship
to parameter:
33.001
34.011
Parameter
manual:
P. xy
Transfer status:
2
min.: 100 Own value
(to be entered!)
max.: 201
def.: 100
Selection of the control method:
100 = open-loop asynchronous motor
200 = open-loop synchronous motor
34.020 Flying restart Unit:
Relationship
to parameter:
34.021
Parameter
manual:
P. xy
Transfer status:
2
min.:
0 Own value
(to be entered!)
max.: 1
def.: 1
This parameter can be used to activate the flying restart.
0 = disable
1 = enable