Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 89
5.3.9 Virtual output
The virtual output can be parameterised like a relay and is available as an option with the following
parameters:
1.131 Software enable / 1.150 Direction of rotation / 1.054 Ramp selection /
5.090 Parameter set change / 5.010 + 5.011 External error 1 + 2
4.230 VO function Unit: integer
Relationship
to parameter:
1.054
1.131
1.150
4.231
4.232
5.010 / 5.011
5.010 / 5.011
5.090
Parameter
manual:
P. xy
Transfer status:
2
min.:
0 Own value
(to be entered!)
max.: 51
def.: 0
(V 03.70 and higher)
Selection of the process variable to which the output should switch.
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
17
18
19
20
21
22
23
24
25
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
=
Not assigned / INVEOR soft PLC
Intermediate circuit voltage
Grid voltage
Motor voltage
Motor current
Actual frequency value
-
-
IGBT temperature
Inner temperature
Error (NO)
Error inverted (NC)
Limit steps enable
Digital input 1
Digital input 2
Ready for operation (mains supply on, no HW enable, motor
stationary)
Ready (mains supply on, HW enable set, motor stationary)
Operation (mains supply on, HW enable set, motor running)
Ready for operation + Ready
Ready for operation + Ready + Operation
Ready + Operation
Motor rating
Torque
Fieldbus (V 03.84 and higher)
Table continues on next page