Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 65
5.3 Application parameters
5.3.1 Basic parameter
1.020 Minimum frequency Unit: Hz
Relationship
to parameter:
1.150
3.070
3.080
Parameter
manual:
S.xy
Transfer status:
2
min.:
0 Own value (to be
entered!)
max.: 400
def.: 0
The minimum frequency is the frequency which is supplied by the drive
controller as soon as it is enabled and there is no additional target value.
The frequency falls below this level if:
a)
the drive accelerates from stationary
b)
the frequency converter is blocked. The frequency then falls to 0 Hz
before it is blocked.
c)
the frequency converter reverses (1.150). The field of rotation reverses at
0 Hz.
d)
the standby function (3.070) is active.
1.021 Maximum frequency Unit: Hz
Relationship
to parameter:
1.050
1.051
Parameter
manual:
S.xy
Transfer status:
2
min.: 0 Own value
(to be entered!)
max.: 400
def.: 50
The maximum frequency is the highest frequency produced by the inverter
depending on the target value.
1.050 Deceleration time 1 Unit: s
Relationship
to parameter:
1.021
1.054
Parameter
manual:
S.xy
Transfer status:
2
min.: 0.1 Own value
(to be entered!)
max.: 1000
def.: 5
Deceleration time 1 is the time that the drive controller needs to brake to 0 Hz
from the max. frequency (1.021).
If the set deceleration time cannot be reached, the fastest possible
deceleration time is implemented.