Parameters
96 Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN
5.201 Save MMI display Unit: integer
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
2
min.: 1 Own value
(to be entered!)
max.: 5
def.: 1
(V 03.80 and higher)
The status screen displayed in the MMI can be selected here.
1 = status 01: Target / actual frequency / motor current
2 = status 02: Speed / motor current / process value 1
3 = status 03: Speed / motor current / process value 2
4 = status 04: Speed / PID target value / PID actual value
5 = status 05: Customer PLC output variable 1 / 2 / 3
5.202 MMI password Unit: integer
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
2
min.: 0 Own value
(to be entered!)
max.: 9999
def.: 0
(V 03.88 and higher)
A password can be allocated here, which is requested when expert mode is
selected in the MMI.
0: Password request deactivated
The password can be individually set in both data sets.
5.4.2 Field bus
6.060 Fieldbus address Unit: integer
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
0
min.: 0 Own value
(to be entered!)
max.: 127
def.: 0
The fieldbus address can be set here.
A change to the fieldbus address is only undertaken once INVEOR is restarted