Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 97
6.061 Set field bus baud rate Unit: integer
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
2
min.: 0 Own value
(to be entered!)
max.: 8
def.: 2
Only for CanOpen:
0 = 1 MBit,
2 = 500 kBit,
3 = 250 kBit,
4 = 125 kBit,
6 = 50 kBit,
7 = 20 kBit,
8 = 10 kBit
6.062 Set bus time-out Unit: s
Relationship
to parameter:
Parameter
manual:
P. xy
Transfer status:
2
min.: 0 Own value
(to be entered!)
max.: 100
def.: 5
Bus timeout, if no fieldbus telegram is received after the set time has expired, the
INVEOR shuts down with the "Bus timeout" error.
The function is only activated once a telegram has been successfully received.
0 = Monitoring disabled
Changing a parameter value via the fieldbus includes direct EEPROM write access.