Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 29
3.3 Installation requirements
3.3.1 Suitable ambient conditions
Conditions Values
Altitude of the installation location: up to 1000 m above sea level / over 1000 m with reduced
performance (1 % per 100 m) (max. 2000 m), see chapter 8.2
Ambient temperature: -10 °C to +40 °C (different ambient temperatures may be
possible in individual cases), see chapter 8.2
Relative air humidity ≤ 96 %, condensation not permitted.
Resistance to vibration and shock: DIN EN 60068-2-6 severity 2 (max. 50 m/s²; 5…200 Hz)
DIN EN 60068-2-27 (300 m/s²)
Electromagnetic compatibility: Immune to interference acc. to DIN EN 61800-3
Cooling: Surface cooling
Tab. 1: Ambient conditions
Ensure that the housing type (protection class) is suitable for the operating environment:
- Ensure that the seal between the motor and the adapter plate is inserted correctly.
- All unused cable screw connections must be sealed.
- Check whether the drive controller's cooling elements have been closed and screwed
down to the adapter plate with the following torque, size α (4 x T20 4 x 35) 1.2 Nm.
Although the drive controller can, in principle, be painted later on, the user must nevertheless
check the material compatibility of the intended paint.
DAMAGE TO PROPERTY POSSIBLE
Failure to comply with this requirement may eventually result in the loss of the protection class
(particularly in respect to seals and fibre-optic elements).