Parameters
Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN 73
5.3.2 Fixed frequency
This mode has to be selected in parameter 1.100, see also the section on selecting the operating
mode.
2.050 Fixed frequency mode Unit: integer
Relationship
to parameter:
1.100
2.051 to 2.057
Parameter
manual:
P. xy
Transfer status:
2
min.: 0 Own value
(to be entered!)
max.: 4
def.: 2
Selection of the digital inputs used for fixed frequencies
1 = Digital In 1, 2
(Fixed frequency 1) (2.051)
(Fixed frequencies 1 - 3) (2.051 to 2.053)
3 = foil keypad (key 1 = fixed frequency 1 / key 2 = fixed frequency 2)
4 = fixed frequency (key I = fixed frequency 1 / key II = fixed frequency 2)
storing (V 03.70 and higher)
2.051 to 2.057 Fixed frequency Unit: Hz
Relationship
to parameter:
1.020
1.021
1.100
1.150
2.050
Parameter
manual:
P. xy
Transfer status:
2
min.:
- 400 Own value
(to be entered!)
max.: + 400
def.: 0
The frequencies that are to be output at the digital inputs 1 - 3 specified in
parameter 2.050 depending on the switching patterns.
See chapter 5.2.1 Explanation of operating modes / fixed frequency.