Parameters
72 Operating manual for INVEOR α | DOC01539818 - 0004 | 2017-01 | V2.0 EN
1.182
Number of automatic
acknowledgements
Unit:
Relationship
to parameter:
1.180
1.181
Parameter
manual:
P. xy
Transfer status:
2
min.: 0 Own value
(to be entered!)
max.: 500
def.: 5
In addition to the automatic acknowledgement function (1.181), it is possible
to limit the maximum number of automatic acknowledgements here.
0
= no restriction on automatic acknowledgements
> 0
= maximum number of automatic
acknowledgements permitted
The internal counter for automatic acknowledgements already undertaken is reset if the motor is
operated for the "maximum number of acknowledgements x auto acknowledgement time"
period without any errors occurring (motor current > 0.2 A).
Example of resetting the auto acknowledgement counter
max. number of acknowledgements = 8
auto acknowledgement time = 20 sec.
After 160 sec. of motor operation without errors, the internal counter for "auto
acknowledgements" undertaken is reset to "0".
In this example, 8 "auto acknowledgements" were accepted.
If an error occurs within the 160 sec., "error 22" is triggered on the 9th acknowledgement
attempt.
This error has to be acknowledged manually by switching off the mains.