1.  If your working condition necessitates the server being powered off or you intend to power off, make 
sure that the power cord is disconnected.
S002 
CAUTION: 
The power-control button on the device and the power switch on the power supply do not turn off 
the electrical current supplied to the device. The device also might have more than one power 
cord. To remove all electrical current from the device, ensure that all power cords are 
disconnected from the power source.
Note: Under certain circumstances, powering off the server is not a prerequisite. Refer to the 
precautions before conducting any tasks.
2.  Check the power cord.
•  Make sure that the third-wire ground connector is in good condition. Use a meter to measure third- 
wire ground continuity for 0.1 ohm or less between the external ground pin and the frame ground.
•  Make sure that the power cord is the correct type. 
To view the power cords that are available for the server: 
a.  Go to:
http://dcsc.lenovo.com/#/
b.  Click Preconfigured Model or Configure to order.
c.  Enter the machine type and model for your server to display the configurator page.
d.  Click Power ➙ Power Cables to see all line cords.
•  Make sure that the insulation is not frayed or worn.
3.  Check for any obvious non-Lenovo alterations. Use good judgment as to the safety of any non-Lenovo 
alterations.
4.  Check inside the server for any obvious unsafe conditions, such as metal filings, contamination, water or 
other liquid, or signs of fire or smoke damage.
5.  Check for worn, frayed, or pinched cables.
6.  Make sure that the power-supply cover fasteners (screws or rivets) have not been removed or tampered 
with.
System reliability guidelines
Review the system reliability guidelines to ensure proper system cooling and reliability.
Make sure the following requirements are met:  
•  When the server comes with redundant power, a power supply must be installed in each power-supply 
bay.
•  Adequate space around the server must be spared to allow server cooling system to work properly. Leave 
approximately 50 mm (2.0 in.) of open space around the front and rear of the server. Do not place any 
object in front of the fans. 
•  For proper cooling and airflow, refit the server cover before you turn the power on. Do not operate the 
server for more than 30 minutes with the server cover removed, for it might damage server components.
Chapter 5. Hardware replacement procedures 57