Network of several drives
8200SHB019910-6
10.2.4 Fuses and cable cross-sections for a network of several
drives
The table values are valid for the operation of 821X/822X/824X controller in
DC-bus operation with PDC100 %, i.e. use of the max. rated controller power on
the DC-bus level (see page 10-10).
For operation with reduced power, it is possible to select smaller fuses and cable
cross-sections.
Type
821X/822X/824X: Mains input L1, L2,L3, PE DC input +V
DC
,-V
DC
,PE
Operation with mains filter/mains choke
Fuse
F1, F2, F3
E.l.c.b. Cable cross-section
1)
Fuse
F4, F5
Cable cross-section
1)
VDE UL VDE mm
2
AWG mm
2
AWG
8211 M6A - B6A 1 17 6.3A 1 17
8212 M6A - B6A 1 17 6.3A 1 17
8213 M 10A - B 10A 1.5 15 12A 1.5 15
8214 M 10A - B 10A 1.5 15 12A 1.5 15
8215 M 16A - B 13A 2.5 13 16A 2.5 13
8216 M 16A - B 16A 2.5 13 20A 4 11
8217 M 32A - B 32A 6 10 40A 6 10
8218 M 32A - B 32A 6 10 40A 6 10
8221 M 50A 50A - 16 5 80A 16 7
8222 M 80A 80A - 25 3 100A 25 5
8223 M 80A 80A - 25 3 100A 25 3
8224 M 125A 125A - 70 2/0 2x 100A
2)
2x 25 (1x 70) 2x 3 (1x 2/0)
8225 M 125A 125A - 70 2/0 2x 100A
2)
2x 25 (1x 70) 2x 3 (1x 2/0)
8226 M 160A 175A - 95 3/0 3x 80A
2)
3x 16 (1x 95) 3x 5 (1x 3/0)
8227 M 200A 200A - 120 4/0 3x 100A
2)
3x 25 (1x 120) 3x 3 (1x 4/0)
8241 M6A 5A B6A 1 17 6.3A 1 17
8242 M6A 5A B6A 1 17 6.3A 1 17
8243 M 10A 10A B 10A 1.5 15 12A 1.5 15
8244 M 10A 10A B 10A 1.5 15 12A 1.5 15
8245 M 16A 20A B 16A 2.5 13 20A 4 11
8246 M 32A 25A B 32A 6 10 40A 6 10
1)
Observe national and regional regulations (e.g. VDE/EVU)!
2)
F4, F5 are possible because of parallel fuse connection.
Parallel connection cables can be used accordingly.