Installation
8200SHB01994-28
4.2.7 Power connections
4.2.7.1 Mains connection
Types 8221 to 8227 Types 8241 to 8246
PE
+UG
-UG
L1
L2
L3
PE
L1 L2 L3
-UG+UG
➀
➁
s
Correct screen connection with screened cables:
-
Connect the screen with suitable clamp to the
conducting control cabinet mounting plate.
-
To improve the screen connection: Connect screen
additionally to the stud next to the power connections.
Correct screen connection with screened cables
(required parts in the accessory kit):
-
Screw sreen plate ➀ on fixing bracket ➁.
-
Fixscreenusing cable lugs. Do not use as a strain
relief!
-
To improve the screen connection: Connect the screen
additionally to the stud next to the power connections.
FIG 4-16 Proposal for mains connection 822X/824X
- Connect the mains cables to the screw terminals L1, L2, L3.
- Connect cables for brake unit (935X), supply module (934X) or further
controllers in the DC-bus connection to the screw terminals +U
G
,-U
G
at the
top of the controller.
- Max. permissible cable cross-sections and tightening torques:
Terminals
Type
Max. permissible
cable cross-sections
L1, L2, L3, +U
G
,-U
G
PE connection
8201 - 8214 2.5 mm
2
0.5 ... 0.6 Nm (4.4 ... 5.3 lbin) 1.7 Nm(15 lbin)
8215 - 8218 4mm
21)
0.5 ... 0.6 Nm (4.4 ... 5.3 lbin) 1.7 Nm(15 lbin)
8221 - 8223 25 mm
22)
4 Nm (35 lbin)
8224 - 8225 95 mm
22)
7 Nm (62 lbin)
8226 - 8227 120 mm
22)
12 Nm (106.2 lbin)
8241 - 8246 4mm
21)
0.5 ... 0.6 Nm (4.4 ... 5.3 lbin) 3.4 Nm(30 lbin)
1)
With pin-end connector: 6 mm
2
With wire c rimp c ap: 4 mm
2
2)
With ring cable lug: The cross-section is only limited by the cable cut-out in the housing.
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com