Technical Data
8200SHB01993-22
3.6.2 Single drives with 150 % overload
The table values are valid for the operation of 82XXcontrollers as single drives with
a matching motor and 150 % overload.
Type
Mains input L1, N, PE / motor connection U, V, W, PE
Operation without mains filter/mains choke Operation with mains filter/mains choke
Fuse
F1, F2, F3
E.l.c.b. Cable cross-section
1)
Fuse
F1, F2, F3
E.l.c.b. Cable cross-section
1)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG
8201 M10A - C 10A 1.5 15 M10A - C 10A 1.5 15
8202 M15A - C 16A 2.5 13 M15A - C 16A 2.5
[1.5]
13
[15]
8203 M20A - C 20A 4 11 M 15A - C 16A 2.5
[1.5]
13
[15]
8204 - - - - - M20A - C 20A 4
[2.5]
11
[13]
Values in square brackets are valid for motor connection
Type
Mains input L1, L2, L3, PE / motor connection U, V, W, PE
Operation without mains filter/mains choke Operation with mains filter/mains choke
Fuse
F1, F2, F3
E.l.c.b. Cable cross-section
1)
Fuse
F1, F2, F3
E.l.c.b. Cable cross-section
1)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG
8211 M6A - B6A 1 17 M6A - B6A 1 17
8212 M10A - B6A 1.5 15 M6A - B6A 1 17
8213 M10A - B 10A 1.5 15 M10A - B 10A 1.5 15
8214 - - - - - M10A - B 10A 1.5 15
8215 M16A - B 16A 2.5 13 M16A - B 13A 2.5 13
8216 M25A - B 25A 6 10 M 20A - B 20A 4 11
8217 M32A - B 32A 6 10 M 25A - B 25A 6 10
8218 - - - - - M32A - B 32A 6 10
Type
Mains input L1, L2, L3, PE / motor connection U, V, W, PE
Operation without mains filter/mains choke Operation with mains filter/mains choke
Fuse
F1, F2, F3
E.l.c.b. Cable cross-section
1)
Fuse
F1, F2, F3
E.l.c.b. Cable cross-section
1)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG
8221 63A -- -- 16 5 M35A 35A -- 10 7
8222 -- -- -- -- -- M 50A 50A -- 16 5
8223 -- -- -- -- -- M 80A 80A -- 25 3
8224 -- -- -- -- -- M 100A 100A -- 50 0
8225 -- -- -- -- -- M 125A 125A -- 70 2/0
8226 -- -- -- -- -- M 160A 175A -- 95 3/0
8227 -- -- -- -- -- M 200A 200A -- 120 4/0
8241 M6A 5A B6A 1 17 M6A 5A B6A 1 17
8242 M6A 5A B6A 1 17 M6A 5A B6A 1 17
8243 M10A 10A B 10A 1.5 15 M10A 10A B 10A 1.5 15
8244 -- -- -- -- -- M 10A 10A B 10A 1.5 15
8245 M25A 25A B 25A 6 10 M20A 20A B 20A 4 11
8246 -- -- -- -- -- M 32A 25A B 32A 6 10
1)
Observe national and regional regulations (e.g. VDE/EVU)!