Commissioning
8200SHB01995-2
5.2 Short commissioning (factory setting)
5.2.1 Switch-on sequence
Step
1. Connect to the mains. The controller is ready for operation after approx. 2 seconds.
2. Enter the direction of rotation.
-
CWrotation:
- Apply a LOW signal to terminal E4 (0 ... + 3 V).
-
CCWrotation:
- Apply a HIGH signal to terminal E4 (+ 12 ... + 30 V).
3. Enter the setpoint. Apply a voltage 0 ... +10 V to terminal 8.
4. Enable controller. Apply a HIGH signal (+12 ... + 30 V) to terminal 28.
5. The drive is now running with factory setting.
5.2.2 Factory setting of the most important drive parameters
Setting Code Factory setting Adaptation to the
application
Operating mode C001 -0- Setpoint selection via terminal 8
Control via terminals
Parameter settingvia 8201BB
See code table, chapter 7.8
for “Standard”
See code table, chapter 7.9
for “HVAC”
Terminal configuration C007 -0- E4 E3 E2 E1
CW/CCW DC injection brake JOG1/2/3
See code table, chapter 7.8
for “Standard”
See code table, chapter 7.9
for “HVAC”
Machine data Chapter 5.3 ff.
Speed range
Min. field frequency C010 0.00 Hz
Chapter5.3.1