EasyManua.ls Logo

Lenze 8200 - Fuses and Cable Cross-Sections; Protection of the Motor Cables

Lenze 8200
313 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
8200SHB0199
3-21
3.6 Fuses and cable cross-sections
3.6.1 Operation of controllers in UL-approved systems
- Use only UL-approved fuses and fuse holders:
- 500 V to 600 V in the mains input (AC, F1 ... F3),
- 700 V in the voltage DC bus (DC, F4/F5),
- Activation characteristic ”H or ”K5”.
- Only use UL-approved cables
Note!
- UL-approved fuses and fuse holder are produced and sold by e.g.
Gemballa Electronics GmbH in Kaltenkirchen, Germany.
- DC fuses as part of the Lenze accessories are UL approved.
3.6.1.1 Protection of the motor cables
- For functional reasons, the motor cables need not to be protected by fuses
if you only connect a motor per controller.
- If you want to drive several motors in parallel connected to a controller, an
individual cable protection is required when reducing the cable
cross-section.
- Refer to the data listed in Operation with mains filter/mains choke”
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Table of Contents

Other manuals for Lenze 8200

Related product manuals