Configuration
8200SHB01997-6
7.3.1 Change and store parameters with the 8201BB operating
module
Acceptance without acknowledgement (ONLINE)
The controller accepts the changed parameter immediately.
1. Change from the operating level to the code level by pressing PRG.
2. Select a code with or .
3. Change to parameter set PAR1 by pressing SH.
- If necessary, press SH again to change to parameter set PAR 2.
4. If PAR1 or PAR2 is blinking, change the parameter with or .
- The controller accepts the changed parameter immediately.
- Thisisalsopossibleduringoperationofthedrive.
5. Change to the code level by pressing SH.
6. Change to the operating level by pressing PRG.
The changed parameter is now stored permanently.
Acceptance acknowledged with SH + PRG
(Labelled with ¤ in the code table.)
The controller accepts the changed parameter only after pressing SH+PRG.
1. Change from the operating level to the code level by pressing PRG.
2. Select a code with or .
3. Change to parameter set PAR1 by pressing SH.
- If necessary, press SH again to change to parameter set PAR 2.
4. If PAR1 or PAR2 is blinking, change the parameter with or .
- Thisisalsopossibleduringoperationofthedrive.
5. Press SH + PRG.
- STO is displayed for approx. 1 s.
- The program jumps back to the code level.
- The controller now works with the new parameter.
6. Change to the operating level by pressing PRG.
The changed parameter is now stored permanently.