EasyManua.ls Logo

Lenze 8200 - 7.5.10.3 Frequency Precontrol; 7.5.10.4 Frequency Setting Range

Lenze 8200
313 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Configuration
8200SHB0199
7-39
7.5.10.3 Frequency precontrol
Code Name Possible settings IMPORTANT
C
o
d
e
N
a
m
e
Lenze Choice Info
I
M
P
O
R
T
A
N
T
C238¤ Frequency
precontrol
-1- -0- No precontrol
-1- With setpoint precontrol
Function C238 = -1-
-
The process controller has only limited influence on the process.
The following setpoint precontrol is possible:
A The setpoint of the process controller is derived from the precontrol value (C181 = 0).
- Applications with frequency precontrol are e.g. speed controls.
B The setpoint of the process controller is selected under C181 (C181 0).
- Applications are e.g. dancer controls, pressure and flow-rate controls
7.5.10.4 Frequency setting range
Code Name Possible settings IMPORTANT
C
o
d
e
N
a
m
e
Lenze Choice Info
I
M
P
O
R
T
A
N
T
C239¤ Frequency setting
range
-0- -0- Bipolar
-1- Unipolar
Function C239 = -0-
-
Allows both directions of rotations for the control process.
C239 = -1-
-
Allows only one direction of rotation for the control process.
Application with frequency setting range are, for instance:
-
Fan controls
-
Dancer controls
Important Only if C005 > -0-, C239 has an influence.