Network of several drives
8200SHB019910-2
10.2 Conditions for trouble-free network operation
Stop!
- The installation and assembly notes must be applied (chapter 4).
- Connect controllers only when they have similar DC-bus/mains-voltage
ranges (see the following table).
- Adapt the thresholds of brake units and input and feedback modules.
- All supplies should only be operated with the prescribed mains
chokes/mains filters! (See page 10-11)
10.2.1 Possible combinations
Possible combinations of Lenze controllers in DC-bus connection:
Type Data 820X 821X 822X 824X 93XX
820X
**)
➀
1 / N / PE / AC / 190 ... 260 V á0%/50Hz/60Hz
➁
270 V ... 360 V
➂
375 V
821X
➀
3 / PE / AC / 320 ... 510 V á0%/50Hz/60Hz
➁
450 V ... 715 V
➂
725 V
*)
822X
➀
3 / PE / AC / 320 ... 528 V á0%/50Hz/60Hz
➁
460 V ... 740 V
➂
725/765 V
*)
824X
➀
3 / PE / AC / 320 ... 528 V á0%/50Hz/60Hz
➁
460 V ... 740 V
➂
725/765 V
*)
93XX
➀
3 / PE / AC / 320 ... 528 V á0%/50Hz/60Hz
➁
460 V ... 740 V
➂
725/765 V
*)
➀ Max. permissible mains-voltage range
➁ DC-bus voltage range
➂ Operating threshold - brake unit
*)
Set the thresholds of all units connected to the DC-bus to the same value.
Procedure: See the corresponding Operating Instructions.
**)
Central supply only possible from a DC source