Configuration
8200SHB01997-38
7.5.10.1 Reset integral component and influence
Function The following functions are possible:
-
Reset the integral component K
I
of the PID controller via terminal.
-
Set the influence of the PID controller to 0.
Activation C007 = -28- ... -34-, -48-, -50-, -51-:
-
HIGHlevelatterminalE2
- Reset of K
I
C007 = -48-, -49-, -50-:
-
HIGHlevelatterminalE4
- Reset influence
The signal levels are indicated for C114 = -0- (see chapter 7.5.14.1)
7.5.10.2 Setpoint selection for the process controller
Code Name Possible settings IMPORTANT
C181* Setpoint PID
controller
0.00 -480.00 {0.02 Hz} 480.00
Function Selection of a frequency setpoint, e.g. for
-
the dancer position for a dancer control in a line drive,
-
the pressure setpoint in a pressure control.
Adjustment C181 = 0
-
The setpoint of the PID controller is
- selected externally (terminal 8 or E1),
- set via the keys (▲, ▼)of the operating module 8201BB.
C181 0
-
Setpoint selection for the PID controller via this code.
Important
-
The setpoint selection via this code is only active, if C181 0.
-
C181 is only stored in parameter set 1.
Special features
-
The setpoint can also be entered as application datum (C500, C501)(see chapter 7.6.3).