Configuration
8200SHB01997-40
7.5.11 Setpoint input
7.5.11.1 Analog setpoint input
Code Name Possible settings IMPORTANT
C
o
d
e
N
a
m
e
Lenze Choice Info
I
M
P
O
R
T
A
N
T
C026 Offset adjustment
analog input
0.00 -10.00 {0.01 V} 10.00 HVAC only Not effective with
C005 = -0-
C027 Scaling factor of
analog input
100.0 -200.0 {0.1 %} 200.0 HVAC only Not effective with
C005 = -0-
C034¤ Master current -0- -0- 0 mA ... 20 mA /
0 V... 5 V/ 0 V... 10 V
-1- 4 mA ... 20 mA
Function An analog setpoint signal can be selected via terminal 8.
-
You can select different setpoint ranges by reconnection of the jumper at the front of the
controller.
-
Inverse setpoint input because of negative terminal adjustment.
-
Offset adjustment of the analog channel (only series “HVAC”)
Adjustment
Setpoint range
Jumper position
0 mA ... 20 mA / 4 mA ... 20 mA
0V...5V
0 V... 10 V
5-6
3-4
1 - 2 (Factory setting)
To select the setpoint by means of the master current, you change the ranges under C034:
C034 = -0- 0 mA ... 20 mA
C034 = -1- 4 mA ... 20 mA
Important
-
With an internal reference voltage of 5 V:
-Pluginthejumperatposition3-4
-
If the setpoint is input by means of a master voltage 0 V ... 5 V / 0 V ... 10 V:
- Set C034 = -0-
-
Analog setpoint input is not possible with setpoint input via the function Motor potentiometer”
(C007 = -10-, -11-, -12-, -13-, -21-).