Technical Data
8200SHB01993-18
3.5 Rated data (Operation with 120 % overload)
3.5.1 Operating conditions
- Applications:
- Pumps with square characteristic
-Fans
- Operation only
- with mains filter or mains choke,
- withmainsvoltage3AC/400V/50Hz/60Hz,
- 821X with chopper frequencies { 8kHz,
- 822X/824X with chopper frequencies = 4 kHz (chopper
frequencies { 16 kHz possible, load-dependent derating).
- Automatic chopper-frequency reduction to 4 kHz.
- Adapt mains-side accessories to the increased mains current:
- Fuses and cable cross-sections, see chapter 3.6.3.
- For data of other components, see ”Accessories”.
3.5.2 Types 821X
120 % overload Type 8211 8212 8213 8214 8215 8216 8217 8218
Rated mains current
with mains filter/mains choke
I
r
[A]
3.0 3.9 7.0 7.0 12.0 12.0 20.5 20.5
Data for mains operation with 3 AC / 400 V/ 50 Hz/60 Hz ; 450 V $ V
DC
$ 650 V
Motor power (4 pole ASM)
P
r
[kW] 1.1 1.5 3.0 3.0 5.5 5.5 11.0 11.0
current
for 60 s
2)
8kHz
*1)
I
Nm
[A] 3.6 5.9 8.3 11.0 14.1 19.5 24.8 35.3
Power loss P
loss
[W] 65 75 100 100 200 200 400 400
1)
Only with variant “HVAC”
* No dyn. chopper frequency derating of the inverter
All other data, see chapter 3.4.2 and chapter 3.4.3.