Configuration
8200SHB0199
7-43
7.5.11.3 Setpoint input via JOG frequencies
Code Name
Possible settings
IMPORTANT
Lenze Choice Info
C037 JOG value 1 20.00 0.00 {0.02 Hz} 480.00
-480.00 {0.02 Hz} 480.00 HVAC only
C038 JOG value 2 30.00 0.00 {0.02 Hz} 480.00
-480.00 {0.02 Hz} 480.00 HVAC only
C039 JOG value 3 40.00 0.00 {0.02 Hz} 480.00
-480.00 {0.02 Hz} 480.00 HVAC only
Function The setpoint input via JOG frequencies is only active, if C007 is set accordingly
(series “Standard”: see chapter 7.8, “Code table”; series “HVAC”: see chapter 7.9, ”Code table”).
Activate
-
JOG value 1 via control terminal E1 or
-
binary coded up to three JOG frequencies via the control terminals E1 and E2.
Activation
Series “Standard”:
-
C007 = -3-, -4-, -5-, -6-, -9-, -14-, -15-, -20-, -22-:
Function E1
Other setpoint source LOW
JOG 1 active HIGH
-
C007 = -0-, -1-, -2-, -16-:
Function E1 E2
Other setpoint source LOW LOW
JOG 1 active HIGH LOW
JOG 2 active LOW HIGH
JOG 3 active HIGH HIGH
Series “HVAC”:
-
C007 = -0-, … -6-, -9-, -14-, -15-, -16-, -20-, -22-, -28-, -29-,
-30-, -35-, -37- … -41-, -46-, -47-, -49-, -50:
Function
EX
Other setpoint source LOW
JOG 1 active HIGH
or
Function
E1 (E3) E2 (E4)
Other setpoint source LOW LOW
JOG 1 active HIGH LOW
JOG 2 active LOW HIGH
JOG 3 active HIGH HIGH
Important
-
The setting of f
dmax
(C011)limits the fieldfrequencyalso for JOG values.
-
The setting of f
dmin
(C010)is not effective for setpoint input by means of JOG values.
Special features The display value of the parameter can be related to anapplicationdatum (C500, C501)
(see chapter 7.6.3).