Troubleshooting and fault elimination
8200SHB01998-4
8.4 Reset of fault messages
TRIP
After eliminating the fault, the pulse inhibit will only be reset after the
acknowledgement of TRIP.
Note!
IftheTRIPsourceisstillactive,theTRIPcannotbereset.
Code Name Possible settings IMPORTANT
C
o
d
e
N
a
m
e
Lenze Choice Info
I
M
P
O
R
T
A
N
T
C170¤ TRIP-reset selection -0- TRIP reset by pressing the STP key
or LOW signal at ctrl. enable or
fieldbus
-1- Auto-TRIP reset or TRIP reset by
pressing the STP key or LOW signal
at ctrl. enable or fieldbus
C171 Deceleration for
Auto-TRIP reset
0.00 0.00 {0.01 s} 60.00
Function You can select whether the fault is tobe reset automaticallyor manually.
Auto-TRIP reset does not reset all faults automatically.
Activation C170 = -0-:
-
TRIP reset (fieldbus)
-
STP key
-
LOW signal at terminal 28
C170 = -1-:
-
Auto-TRIP reset resets all faults after the time set under C171.
-
TRIP reset (fieldbus)
-
STP key
-
LOW signal at terminal 28
Important
-
Mains switching always resets TRIP.
-
With more than 8 auto-TRIP resets within 10 minutes (internal counter), the controller sets TRIP
and indicates rST (counter exceeded).
- With TRIP reset by pressing the STP key or LOW signal at ctrl. enable or fieldbus, the controller
resets the internal counter.