Configuration
8200SHB01997-10
7.4.2 Working with parameter sets
Code Name
Possible settings
IMPORTANT
Lenze Choice Info
[C002]* Parameter set -0- Function executed
-1- Overwrite PAR1 with factory setting
-2- Overwrite PAR2 with factory setting
-3- Overwrite PAR1 and PAR2 with the
data of the operating module
-4- Overwrite PAR1 with the data of the
operating module
-5- Overwrite PAR2 with the data of the
operating module
-6- Transmit PAR1 and PAR2 to the
operating module
-7- Overwrite PAR1, PAR2 and the
unit-dependent data (C016, C036,
C088, C091)with the data of the
operating module.
HVAC only
[C007]* Te r mi n a l
configuration
-0- E4 E3 E2 E1
-1- CW/CCW PAR JOG1/2/3
-3- CW/CCW PAR DCB JOG1
-4- CW/CCW QSP PAR JOG1
-6- CW/CCW PAR TRIP set JOG1
-7- CW/CCW PAR DCB TRIP set
-8- CW/CCW QSP PAR TRIP set
-12- CW/CCW PAR UP DOWN
-15- CCW/QSPCW/QSP PAR JOG1
-17- CCW/QSPCW/QSP PAR DCB
-18- CCW/QSPCW/QSP PAR TRIP set
-24- H/Re PAR UP DOWN
-33- QSP PAR I-OFF D/F
-35- JOG1/2/3 PAR D/F
-36- DCB QSP PAR D/F
-37- JOG1 QSP PAR D/F
-38- JOG1 PAR TRIP set D/F
-44- UP DOWN PAR D/F
-45- CW/CCW QSP PAR D/F
-46- H/Re PAR QSP JOG1
-51- DCB PAR I-OFF D/F
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
HVAC only
For parameter-set
changeover via
terminal, the
corresponding terminal
must be assigned to
PARin both parameter
sets.