4.13 Motor Output Voltage Adjustment
Output voltage settings are required when a motor’s rated voltage differs from the
input voltage to the inverter. Set the voltage value to configure the motor’s rated
operating voltage. The set voltage becomes the output voltage of the inverter’s base
frequency. If bA.15 (motor rated voltage) is set to 0, the inverter corrects the output
voltage based on the input voltage in the stopped condition. If the frequency is higher
than the base frequency, when the input voltage is lower than the parameter setting,
the input voltage will be the inverter output voltage.
Group
Code
Name
Setting
Setting Range
Unit
bA
15
Motor rated voltage
0
0, 100-480
V
4.14 Start Mode Setting
Select the start mode to use when the operation command is input with the motor in
the stopped condition.
4.14.1 Accelerating Start
Acceleration start is a general acceleration mode. If there are no extra settings applied,
the motor accelerates directly to the frequency reference when the command is input.
Group
Code
Name
Setting
Setting Range
Unit
Ad
07
Start Mode
0
Acc
01
-

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals