5.2.2 Jog Operation 2-Fwd/Rev Jog by Multi-Function Terminal
For jog operation 1, an operation command must be entered to start operation, but
while using jog operation 2, a terminal that is set for a forward or reverse jog also
starts an operation. The priorities for frequency, Acc/Dec time and terminal block input
during operation in relation to other operating modes (Dwell, 3-wire, up/down, etc.) are
identical to jog operation 1. If a different operation command is entered during a jog
operation, it is ignored and the operation maintains the jog frequency.
Jog run acceleration
time
Jog run deceleration
time
Px terminal setting
options
5.3 Up-down Operation
The Acc/Dec time can be controlled through input at the multi-function terminal block.
Similar to a flowmeter, the up-down operation can be applied easily to a system that
uses the upper-lower limit switch signals for Acc/Dec commands.
Up-down operation
frequency save
Px terminal setting
options
The up-down operation will operate only when the multi-function terminal set to U/D