5.2.2 Jog Operation 2-Fwd/Rev Jog by Multi-Function Terminal
For jog operation 1, an operation command must be entered to start operation, but
while using jog operation 2, a terminal that is set for a forward or reverse jog also
starts an operation. The priorities for frequency, Acc/Dec time and terminal block input
during operation in relation to other operating modes (Dwell, 3-wire, up/down, etc.) are
identical to jog operation 1. If a different operation command is entered during a jog
operation, it is ignored and the operation maintains the jog frequency.
Group
Code
Name
Setting
Setting Range
Unit
dr
11
Jog Frequency
10.00
0.50Maximum
frequency
Hz
12
Jog run acceleration
time
20.00
0.00600.00
sec
13
Jog run deceleration
time
30.00
0.00600.00
sec
In
65
69
Px terminal setting
options
46
FWD JOG
052
-
47
REV JOG
5.3 Up-down Operation
The Acc/Dec time can be controlled through input at the multi-function terminal block.
Similar to a flowmeter, the up-down operation can be applied easily to a system that
uses the upper-lower limit switch signals for Acc/Dec commands.
Group
Code
Name
Setting
Setting Range
Unit
Ad
65
Up-down operation
frequency save
1
Yes
01
-
In
6569
Px terminal setting
options
17
Up
052
-
18
Down
20
U/D Clear
27
U/D Enable
The up-down operation will operate only when the multi-function terminal set to U/D