7.2.4 Command Loss Protective Operation
Configure the command loss decision standards and protective operations run when a
communication problem lasts for a specified period of time.
Command Loss Protective Operation Setting Details
Select the operation to run when a communication error has occurred
and lasted exceeding the time set at Pr.13.
The speed command immediately becomes the
operation frequency without any protection
function.
The inverter blocks output. The motor performs in
free-run condition.
The motor decelerates and then stops.
The inverter continues in the speed command
input before the loss of speed.
The inverter continues in the operation frequency
before the loss of speed.
The inverter operates at the frequency set at Pr.
14 (Lost Preset F).
7.2.5 Setting Virtual Multi-Function Input
Multi-function input can be controlled using a communication address (0h0385). Set
codes CM.70–77 to the functions to operate, and then set the BIT relevant to the
function to 1 at 0h0322 to operate it. Virtual multi-function operates independently
from In.65–69 analog multi-function inputs and cannot be set redundantly. Virtual
multi-function input can be monitored using CM.86 (Virt Dl Status). Before you
configure the virtual multi-function inputs, set the DRV code according to the
command source.
Communication multi-
function input x
Communication multi-
function input monitoring
Example: When sending an Fx command by controlling virtual multi-function input in
the common area via Int485, set CM.70 to FX. Then, assign a 0h0001 value to the
communication address 0h0322 to operate the forward direction operation (Fx)
feature.