OU.31 Relay1,
OU.33 Relay 2
Set multi-function output terminal or relay to be used as a timer to 28
(Timer out).
Input a signal (On) to the timer terminal to operate a timer output (Timer
out) after the time set at OU.55 has passed. When the multi-function
input terminal is off, multi-function output or relay turns off after the time
set at OU.56.
5.25 Brake Control
This feature controls the On/Off operation of the load’s electronic braking system.
Brake release Forward
frequency
Brake release Reverse
frequency
Multi-function relay 1 item
Multi-function relay 2 item
When brake control is activated, DC braking (Ad.12) at inverter start and dwell
operation (Ad.20–23) do not operate.
• Brake release sequence: During motor stop state, if an operation command is
entered, the inverter accelerates up to brake release frequency (Ad.44– 45) in
forward or in reverse direction. After reaching brake release frequency, if motor
current reaches brake release current (BR Rls Curr), the output relay or multi-
function output terminal for brake control sends a release signal. Once the signal
has been sent, acceleration will begin after maintaining frequency for brake release