only or to use as NO (Normal Open) and NC(Normal Close). If set to 1:
NO only, the terminal in which the functions are set to Fx/Rx cannot be
set as NC.
If set to 0: NO/NC, terminals set as Fx/Rx can also be set as NC.
Display the configuration of each contact. When a segment is
configured as A terminal using dr.87, the On condition is indicated by
the top segment turning on. The Off condition is indicated when the
bottom segment is turned on. When contacts are configured as B
terminals, the segment lights behave conversely. Terminals are
numbered P1–P5, from right to left.
Bit On when A contact is
set
Bit Off when A contact is set
4.19 Fire Mode Operation
This function is used to allow the inverter to ignore minor faults during emergency
situations, such as fire, and provides continuous operation to fire pumps.
When turned on, Fire mode forces the inverter to ignore all minor fault trips and repeat
a Reset and Restart for major fault trips, regardless of the restart trial count limit.
Fire Mode Parameter Settings
Fire Mode operation
count
Px terminal setting
options
Ad 80. If Fire Mode Sel parameter is selected as Fire Mode and the terminal selected
as 51: Fire Mode in In.65–69 Px terminal feature setup parameter is entered as On
state, the inverter will operate as Fire Mode and Ad 83. Fire Mode Count will be
increased by 1.
The inverter runs in Fire Mode when Ad. 80 (Fire Mode Sel) is set to Fire Mode Test,
and the multi-function terminal (In. 65-69 Px) configured for the fire mode (51: Fire
Mode) is turned on. But when the minor fault trips are ignored or there are major fault