Code and
Features
Description
NO/NC Sel
only or to use as NO (Normal Open) and NC(Normal Close). If set to 1:
NO only, the terminal in which the functions are set to Fx/Rx cannot be
set as NC.
If set to 0: NO/NC, terminals set as Fx/Rx can also be set as NC.
In.90 DI Status
Display the configuration of each contact. When a segment is
configured as A terminal using dr.87, the On condition is indicated by
the top segment turning on. The Off condition is indicated when the
bottom segment is turned on. When contacts are configured as B
terminals, the segment lights behave conversely. Terminals are
numbered P1P5, from right to left.
Items
Bit On when A contact is
set
Bit Off when A contact is set
Keypad
4.19 Fire Mode Operation
This function is used to allow the inverter to ignore minor faults during emergency
situations, such as fire, and provides continuous operation to fire pumps.
When turned on, Fire mode forces the inverter to ignore all minor fault trips and repeat
a Reset and Restart for major fault trips, regardless of the restart trial count limit.
Fire Mode Parameter Settings
Group
Code
Name
Setting
Setting
Range
Unit
Ad
80
Fire Mode selection
1
Fire Mode
02
-
81
Fire Mode frequency
060
060
82
Fire Mode run
direction
01
01
83
Fire Mode operation
count
Not
configurable
-
-
In
6569
Px terminal setting
options
51
Fire Mode
052
-
Ad 80. If Fire Mode Sel parameter is selected as Fire Mode and the terminal selected
as 51: Fire Mode in In.6569 Px terminal feature setup parameter is entered as On
state, the inverter will operate as Fire Mode and Ad 83. Fire Mode Count will be
increased by 1.
The inverter runs in Fire Mode when Ad. 80 (Fire Mode Sel) is set to Fire Mode Test,
and the multi-function terminal (In. 65-69 Px) configured for the fire mode (51: Fire
Mode) is turned on. But when the minor fault trips are ignored or there are major fault