6.3.8 No Motor Trip
If an operation command is run when the motor is disconnected from the inverter
output terminal, a ‘no motor trip’ occurs and a protective operation is performed by the
system.
Group
Code
Name
Setting
Setting
Range
Unit
Pr
31
No motor motion at
detection
0
None
01
-
1
Free-run
-
-
32
No motor detection
current level
5
1100
%
33
No motor detection time
3.0
0.110
sec
No Motor Trip Setting Details
Code and
Features
Description
Pr.32 No Motor
Level,
Pr.33 No Motor
Time
If the output current value [based on the rated current (bA.13)] is
lower than the value set at Pr.32 (No Motor Level), and if this
continues for the time set at Pr.33 (No Motor Time), a ‘no motor trip’
occurs.
If bA.07 (V/F Pattern) is set to 1 (Square), set Pr.32 (No Motor Level) to a value lower
than the factory default. Otherwise, ‘no motor trip’ due to a lack of output current will result
when the ‘no motor trip’ operation is set.
6.3.9 Low Voltage Trip 2
If you set the Pr-82 (LV2 Selection) code to Yes (1), the trip notification is displayed
when a low voltage trip occurs. In this case, even if the voltage of the DC Link
condenser is higher than the trip level, the LV2 trip will not be retrieved. To retrieve
the trip, reset the inverter. The trip history will not be saved.
Grou
p
Code
Name
Setting
Setting Range
Unit
Pr
82
LV2 Selection
Yes (1)
0/1
-

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals