Take caution on any safety accidents when operating the inverter with Power-on Run
enabled as the motor will begin rotating as soon as the inverter starts up.
4.7 Reset and Restart
Reset and restart operations can be setup for inverter operation following a fault trip,
based on the terminal block operation command (if it is configured). When a fault trip
occurs, the inverter cuts off the output and the motor will free-run. Another fault trip
may be triggered if the inverter begins its operation while motor load is in a free-run
state.
Group
Cod
e
Name
Setting
Setting
Range
Unit
Operatio
n
drv
Command Source
1
2
Fx/Rx-1 or
Fx/Rx-2
04
-
Pr
08
Selection of startup on trip
reset
1
Yes
01
09
Number of automatic
restarts
0
010
10
Auto restart delay time
1.0
060
sec
Note
To prevent a repeat fault trip from occurring, set Cn.71 (speed search options) bit 2 to
1. The inverter will perform a speed search at the beginning of the operation.
If the speed search is not enabled, the inverter will start its operation in a normal V/F
pattern and accelerate the motor. If the inverter has been turned on without ‘Reset and
Restart’ enabled, trips must be reset, then turn the terminal block command off and on
to begin the inverter’s operation.

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals