8 Table of Functions
This chapter lists all the function settings for G100 series inverter. Set the parameters
required according to the following references. If a set value input is out of range, the
following messages will be displayed on the keyboard. In these cases, the inverter will
not operate with the [ENT] key.
Set value not allocated: rd
Set value repetition (multi-function input, PID reference, PID feedback related): OL
Set value not allowed (optional value): no
8.1 Operation Group
SL: Sensorless vector control (dr.09), Property: Write-enabled during operation
Code
Comm.
Address
Name
Keypad
Display
Setting
Range
Initial
Value
Property*
V/F
SL
Ref.
-
0h1D00
Target
frequency
0.00
0Maximum
frequency
(Hz)
0.00
O
O
O
p.45
-
0h1D01
Acceleration
time
ACC
0.0600.0
(s)
5.0
O
O
O
p.78
-
0h1D02
Deceleration
time
dEC
0.0600.0
(s)
10.0
O
O
O
p.78
-
0h1D03
Command
Source
drv
0
Keypad
1:
Fx/Rx-1
X
O
O
p.73
1
Fx/Rx-1
2
Fx/Rx-2
3
Int 485
4
Fieldbus
1
-
0h1D04
Frequency
reference
source
Frq
0
Keypad-1
0:
Keypad-
1
X
O
O
p.60
1
Keypad-2
2
V1
4
V0, built-
in volume
5
I2
6
Int 485
8
Field Bus
1
-
0h1D05
Multi-step
speed
frequency 1
St1
0.00
Maximum
frequency
(Hz)
10.00
O
O
O
p.71
-
0h1D06
Multi-step
speed
St2
0.00
Maximum
20.00
O
O
O
p.71
1

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals