Comm.
Address
Parameter
Scale
Unit
Assigned Content by Bit
0h0343
Run Time minute
0
Min
Total number of minutes excluding the
total number of Run Time days
0h0344
Fan Time date
0
Day
Total number of days the heat sink fan
has been running
0h0345
Fan Time minute
0
Min
Total number of minutes excluding the
total number of Fan Time days
0h0346
0h0348
Reserved
-
-
-
0h0349
Reserved
-
-
-
0h034A
Option 1
-
-
0: None, 9: CANopen
0h034B
Reserved
-
-
-
0h034C
Reserved
-
-
-
7.6.2 Control Area Parameter (Read/ Write)
Comm.
Address
Parameter
Scale
Unit
Assigned Content by Bit
0h0380
Frequency command
0.01
Hz
Command frequency setting
0h0381
RPM command
1
Rpm
Command rpm setting
0h0382
Operation command
-
-
B7
Reserved
B6
Reserved
B5
Reserved
B4
Reserved
B3
0 1: Free-run stop
B2
0 1: Trip initialization
B1
0: Reverse direction command,
1: Forward direction command
B0
0: Stop command, 1: Run
command
Example: Forward operation
command: 0003h,
Reverse operation command: 0001h
0h0383
Acceleration time
0.1
sec
Acceleration time setting
0h0384
Deceleration time
0.1
sec
Deceleration time setting
0h0385
Virtual digital input
control
(0: Off, 1: On)
-
-
BI5
Reserved
-
Reserved
B8
Reserved
B7
Virtual DI 8 (CM.77)
B6
Virtual DI 7 (CM.76)
B5
Virtual DI 6 (CM.75)
B4
Virtual DI 5 (CM.74)

Table of Contents