Page #248 background imageLoading...
Page #248 background image
Comm.
Address
Parameter
Scale
Unit
Assigned Content by Bit
B5
Reserved
B4
Reserved
B3
Keypad Lost Command
B2
Lost Command
B1
LV
B0
BX
0h0333
H/W Diagnosis Trip
information
-
-
B15
Reserved
-
Reserved
B6
Reserved
B5
QueueFull
B4
Reserved
B3
Watchdog-2 error
B2
Watchdog-1 error
B1
EEPROM error
B0
ADC error
0h0334
Warning information
-
-
B15
Reserved
-
Reserved
B10
Reserved
B9
Auto Tuning failed
B8
Keypad lost
B7
Encoder disconnection
B6
Wrong installation of encoder
B5
DB
B4
FAN running
B3
Lost command
B2
Inverter Overload
B1
Underload
B0
Overload
0h0335
Latch type trip
information - 3
-
-
B3
Under Torque Detection 2
B2
Over Torque Detection 2
B1
Under Torque Detection 1
B0
Over Torque Detection 1
0H03356
0h033F
Reserved
-
-
-
0h0340
On Time date
0
Day
Total number of days the inverter has
been powered on
0h0341
On Time minute
0
Min
Total number of minutes excluding the
total number of On Time days
0h0342
Run Time date
0
Day
Total number of days the inverter has
driven the motor

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals