5.28 Analog Output
An analog output terminal provides output of 0–10 V voltage and 4–20 mA current.
5.28.1 Current Analog Output
An output size can be adjusted by selecting an output option at AO (Analog Output)
terminal.
Voltage and Current Analog Output Setting Details
Select a constant value for output.
Outputs operation frequency as a standard. 10 V
output is made from the frequency set at dr.20
(Max Freq).
10 V output is made from 200% of inverter rated
current (heavy load).
Sets the outputs based on the inverter output
voltage. 10 V output is made from a set voltage in
bA.15
(Rated V).
If 0 V is set in bA.15, 200 V/240 V/400 V models
output 10 V based on the actual input voltage (480
V).
Outputs inverter DC link voltage as a standard.
Outputs 10 V when the DC link voltage is 410 Vdc
for 200 V models, and 820 Vdc for 400 V models.
Outputs the generated torque as a standard.
Outputs 10 V at 250% of motor rated torque.