3.2.1 Group and Code Selection
Follow the examples below to learn how to switch between groups and codes.
Move to the group you want using the [MODE]
keys. Press the [MODE] key for longer than 1
second to move in the opposite direction.
Move up and down through the codes using the
[▲] and [▼] keys until you locate the code that
you require.
Press the [ENT] key to save the change.
When moving up and down through the codes using the [▲] and [▼] keys in each group,
there are cases where the code number does not increase or decrease. This is because
the number was left blank in the inverter program by expecting additional features or the
program was set up to not display the unused features.
Example) If Ad.24 (frequency limit) code is set to 0 (No), Ad.25 (frequency lower limit
value) and Ad.26 (frequency upper limit value) codes will not be displayed. Ad.24
(frequency limit) code must be set to 1 (Yes) to display Ad.25 (frequency lower limit value)
and Ad.26 (frequency upper limit value) codes.