[Example of auto restart with a setting of 2]
If the auto restart number is set, be careful when the inverter resets from a fault trip. The
motor may automatically start to rotate.
5.15 Operational Noise Settings (Change of Carrier
Frequency Settings)
Group
Code
Name
Setting Range
Unit
Cn
04
Carrier Frequency
0.4kW~4.0kW
2.0~15.0
kHz
5.5kW~7.5kW
1.0~15.0
* PWM: Pulse width modulation
Operational Noise Setting Details
Code and
Features
Description
Cn.04 Carrier
Freq
Adjust motor operational noise by changing carrier frequency settings.
Power transistors (IGBT) in the inverter generate and supply high
frequency switching voltage to the motor. The switching speed in this
process refers to the carrier frequency. If the carrier frequency is set
high, it reduces operational noise from the motor, and if the carrier
frequency is set low, it increases operational noise from the motor.