5.9 Auto-tuning
The motor parameters can be measured automatically and can be used for auto
torque boost or sensorless vector control.
Example - Auto-Tuning Based on 0.75kW, 200V, 60Hz, 4 Pole Motor
Group
Code
Name
Setting
Setting Range
Unit
dr
14
Motor capacity
1
0.75 kW
015
-
bA
11
Number of motor
poles
4
248
-
12
Rated slip speed
70
03000
Rpm
13
Motor rated
current
3.3
1.01000.0
A
14
Motor noload
current
1.7
0.51000.0
A
15
Motor rated
voltage
220
170480
V
16
Motor efficiency
83
64100
%
20
Auto tuning
0
None
-
-
21
Stator resistance
2.951
Depends on the motor
setting
Ω
22
Leakage
inductance
25.20
Depends on the motor
setting
mH
23
Stator
inductance
171.1
Depends on the motor
setting
mH
24
Rotor time
constant
137
255000
ms