Exception Code
Code
01: ILLEGAL
FUNCTION
02: ILLEGAL DATA
ADRESS
03: ILLEGAL DATA
VALUE
06: SLAVE DEVICE
BUSY
Response
Field Name
Station ID
Function*
Exception Code
CRC Lo
CRC Hi
* The function value uses the top level bit for all query values.
Example of Modbus-RTU Communication in Use
When the muti-step acceleration time1 (Communication address 0x1246) is changed to
5.0 sec and the Multi-step deceleration time1 (Communication address 0x1247) is
changed to 10.0 sec.
Frame Transmission from Master to Slave (Request)
Item
s
Statio
n ID
Functio
n
Starting
Address
# of
Registe
r
Byte
Count
Data 1
Data 2
CRC
Hex
0x01
0x10
0x1245
0x0002
0x04
0x0032
0x0064
0x432
4
Desc
riptio
n
CM.01
Int485
St ID
Preset
Multiple
Register
Starting
Address -1
(0x1246-1)
-
-
50
(ACC time
5.0sec)
100
(DEC time
10.0sec)
-
Frame Transmission from Slave to Master (Response)
Item
s
Station ID
Function
Starting Address
# of Register
CRC
Hex
0x01
0x10
0x1245
0x0002
0x5565
Desc
riptio
n
CM.01
Int485 St
ID
Preset
Multiple
Register
Starting Address -1
(0x1246-1)
-
-

Table of Contents

Other manuals for LSIS G100

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS G100 and is the answer not in the manual?

LSIS G100 Specifications

General IconGeneral
BrandLSIS
ModelG100
CategoryInverter Drive
LanguageEnglish

Related product manuals