Output wiring is short-circuited.
There is a fault with the electronic
semiconductor (IGBT).
Do not operate the inverter. Contact
the retailer or the LSIS customer
service center.
A ground fault has occurred in the
inverter output wiring.
The motor insulation is damaged.
The ambient temperature is too low.
Keep the ambient temperature
above –10℃.
There is a fault with the internal
temperature sensor.
Contact the retailer or the LSIS
customer service center.
A foreign object is obstructing the
fan’s air vent.
Remove the foreign object from the
air inlet or outlet.
The cooling fan needs to be replaced.
9.3 Other Faults
When a fault other than those identified as fault trips or warnings occurs, refer to the
following table for possible causes and remedies.
Parameters
cannot be set.
The inverter is in operation (driving
mode).
Stop the inverter to change to
program mode and set the
parameter.
The parameter access is incorrect.
Check the correct parameter
access level and set the
parameter.
The password is incorrect.
Check the password, disable the
parameter lock and set the
parameter.
Check the power input to resolve
the low voltage and set the
parameter.
The motor
does not
rotate.
The frequency command source is
set incorrectly.
Check the frequency command
source setting.
The operation command source is
set incorrectly.
Check the operation command
source setting.
Power is not supplied to the terminal
R/S/T.
Check the terminal connections
R/S/T and U/V/W.
The charge lamp is turned off.
The operation command is off.
Turn on the operation command
(RUN).
Unlock the motor or lower the load