MI 2893 / MI 2892 / MI 2885 Measurement methods
184
Fundamental phase power measurements
Standard compliance: IEEE STD 1459-2010
All fundamental power measurements are calculated from fundamental voltages and currents obtained
from harmonic analysis (see section 5.1.8 for details).
Fundamental phase active power:
pp
IUfundPfundPfundP
IUP
cos
Fundamental apparent and reactive power and power factor are calculated according to the following
equations:
Fundamental phase apparent power:
Fundamental phase reactive power:
pp
IUfundPfundPfundP
IUQ
sin
Phase displacement power factor:
Positive sequence (total) fundamental power measurements
Standard compliance: IEEE STD 1459-2010
According to the IEEE STD 1459, positive sequence power (P
+
, Q
+
, S
+
) are recognised as very important
intrinsic power measurements. They are calculated according to the following equation:
Positive sequence active power:
Positive sequence reactive power:
270
0
+DPFind
Lead
Lag
+DPFcap
-DPFcap
-DPFind
180
0
90
0
0
0
+P-P
-Q
+Q
I
II
III IV